Product model | BCHL-ACB3 | BCHL-ACB4 | BCHL-ACB5 | 9CHL-AC36 |
Number of input channels | 3-Way | 4-Way | 5-Way | 6-Way |
Maximum input voltage AC | 380V/550V/690V | 380V/550V/690V | 380V/550V/690V | 380V/550V/690V |
Maximum input current | 100A | 100A | 100A | 100A |
Maximum output current | 315A | 350A | 400A | 500A |
Lightning protection | C-level lightning protection, nominal 20KA, maximum 40KA | |||
Monitoring module (optional) | Monitor the status of incoming circuit breakers, outgoing circuit breakers, lightning arresters, and monitor output current, voltage, power, temperature inside the box, etc. (Optional) | |||
Communication method | RS485 | |||
Communication protocol | Standard MODBUS-RTU protocol | |||
Signal lightning protection (optional) | Optional | |||
Working environment | Working temperature: -35℃”+70℃, humidity 99%, no condensation | |||
Altitude | ≤2000 meters, more than 2000 meters need to consider capacity reduction. | |||
Power consumption of measurement unit | ≤4W | |||
Auxiliary power supply (optional) | Self-powered, A-phase C-phase line voltage power supply | |||
1. AC 90 ~560V (rated voltage 380V, 480V) | ||||
2. AC 400V~800V (rated voltage 690V) | ||||
Installation method | Wall-mounted installation | |||
Box material | Hot-dip galvanized steel plate/304 stainless steel | |||
Protection level | IP65 | |||
Product model | BCHL-DCB4 | BCHL-DCB8 | BCHL-DCB12 | BCHL-DCB16 |
Number of input channels | 4-Way | B-Way | 12-Way | 16-Way |
Maximum input voltage | 1000VDC/1500VDC | 1000VDC/1500VDC | 1000VDC/1500VDC | 1000VDC/1500VDC |
Maximum input current | 15A | 15A | 15A | 15A |
Maximum output current | 80A | 100A | 160A | 200A |
Detection unit | Detect the current, output voltage, box temperature, lightning arrester status, circuit breaker status of each channel | |||
Communication method | Standard: RS485 | |||
Communication protocol | Standard MODBUS-RTU protocol | |||
Lightning protection | Nominal 20KA, maximum 40KA | |||
Signal lightning protection | Standard | |||
Anti-reverse function | Modular package anti-reverse diode (optional) | |||
Working environment | Working temperature: -35℃~+70℃, humidity 99%, no condensation | |||
Altitude | ≤4000 meters | |||
Power consumption of measurement unit | ≤4W | |||
Auxiliary power supply | No need for external power supply, taken from the box DC100V"DC1000V/DC100V"DC1500V | |||
Installation method | Wall-mounted installation | |||
Box material | Hot-dip galvanized steel plate/304 stainless steel | |||
Protection level | IP65 |
Product model | BC-GGD | |
Rated voltage | AC380V | |
Current range | 315"2000A | |
Inverter capacity | 150~1000KW | |
Number of input channels | 1~6 channels (or customized according to customer requirements) | |
Lightning protection | C-level lightning protection, nominal 20KA, maximum 40KA | |
Long delay protection | Yes | |
Short delay protection | Yes | |
Instantaneous protection | Yes | |
Overvoltage protection | Setting value (250V~300V) can be set, accuracy ±2% | |
Undervoltage protection | Setting value (160V~200V) can be set, accuracy ±2% | |
Ground fault protection | Can be turned on or off | |
Working environment | Working temperature: -25℃+60℃; humidity 99%, no condensation | |
Altitude | ≤2000 meters, more than 2000 meters need to consider capacity reduction. | |
Installation method | Floor installation | |
Box material | Cold-rolled steel plate | |
Protection level | IP30 or IP54 |
|
Product model | BC-XM | BC-XM |
Rated voltage | AC220V | AC380V |
Maximum current | 45A | 60A |
Inverter capacity | 3~10KW | 10~30KW |
Number of input channels | 1-way | 1-way |
Lightning protection | Class C lightning protection, nominal 20KA, maximum 40KA | C-level lightning protection, nominal 20KA, maximum 40KA |
Overcurrent protection | Yes | Yes |
Short circuit protection | Yes | Yes |
Overvoltage protection | AC275V±5V | AC460V±15V |
Undervoltage protection | AC170V±5V | AC300V±15V |
Working environment | Working temperature: -25℃“+60℃: humidity 99%, no condensation | Working temperature: -25℃”+60℃; humidity 99%, no condensation |
Altitude | ≤2000 meters, more than 2000 meters need to consider capacity reduction. | ≤2000 meters, more than 2000 meters need to consider capacity reduction. |
Installation method | Wall-mounted installation | Wall-mounted installation |
Box material | Cold-rolled steel plate/stainless steel | Cold-rolled steel plate/stainless steel |
Protection level | IP54 | IP54 |
Product model | BC-XM | |
Rated voltage | AC380V | |
Current range | 80~200A | |
Inverter capacity | 40~200KW | |
Number of input channels | 1~3 channels (or customized according to customer requirements) | |
Lightning protection | C-level lightning protection, nominal 20KA, maximum 40KA | |
Long delay protection | Yes | |
Short delay protection | Yes | |
Instantaneous protection | Yes | |
Overvoltage protection | Setting value (250V~300V) can be set, accuracy ±2% | |
Undervoltage protection | Setting value (160V~200V) can be set, accuracy ±2% | |
Leakage protection | 100mA, 300mA, 500mA adjustable | |
Working environment | Working temperature: -25℃+60℃; humidity 99%, no condensation | |
Altitude | ≤2000 meters, more than 2000 meters need to consider capacity reduction. | |
Installation method | Wall-mounted installation | |
Box material | Cold-rolled steel plate | |
Protection level | IP54 |