Project |
| Unit | Parameter |
Rated voltage |
| [kV] | 12/24 |
Rated lightning impulse withstand voltage | Phase to phase and phase to ground | [kV] | 75/125 |
Between fractures | [kV] | 85/145 | |
1min power frequency withstand voltage | Phase to phase and phase to ground | [kV] | 42/65 |
Between fractures | [kV] | 48/79 | |
Rated frequency |
| [HZ] | 50/60 |
Rated current | Main bus | [A] | 1250/630 |
Branch bus | [A] | 1250/630 | |
Rated short-time withstand current | Main circuit | [kA] | 20/3S |
Ground loop | [kA] | 20/2S | |
Rated peak withstand current |
| [kA] | 50 |
Transfer current |
| [A] | 1500/800 |
Protection level |
|
| IP3X |
Load switch mechanical life |
| times | 2000 |
Mechanical life of grounding switch |
| times | 2000 |
Load switch cabinet | Cabinet depth | [mm] | 916.940.840 |
Cabinet width | [mm] | 375.500.750 | |
Cabinet height | [mm) | 1635.1885.1600.1800 | |
Low pressure room | Height | [mm] | 350.450 |
Circuit breaker cabinet | Cabinet width | [mm] | 650.750.800 |
Cabinet depth | [mm] | 916.940.840 | |
Cabinet height | [mm] | 1885.1800.2100 |